Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x After the call acknowledgement signals are sent, the two way voice communications shall be available between the car & authorized personnel. Re-inspection required 12/13/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Cab phone line inoperative. 10/15/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 x Door pressure too high, over 30 lbs, needs repair. Re-inspection required 11/30/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Fire service Phase I is not working. Re-inspection required
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Phone in elevator cab does not work. 2/2/2021
A17.1-1996 : Elevators 1.9 - Power closing of doors or gates 112.3 x The bottom car door reopening device (electric eye) was not working on the day of inspection. Repair or replace the reopening device for passenger safety. 12/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. 12/3/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The emergency car lighting is not operational, likely indicating that the back-up power device (battery) has failed. The fixture shall be repaired to operate. Reinspection required. 12/3/2024