MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A17.1-1987 102.2 A sprinkler head has been added to the elevator machine room without the required heat detector to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect.
MO Minimum : Elevators (H) - Machine Rooms (H)2 There are pipes that carry liquids, gases or vapors directly above the elevator controller. These pipes should be guttered to assure that no discharge from these pipes falls onto the elevator equipment.