Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A17.1-1987 102.2 A sprinkler head has been added to the elevator machine room without the required heat detector to activate the shunt trip disconnect before the application of water. Heat detectors shall be installed within 2’ of each sprinkler head to activate the shunt trip disconnect.
MO Minimum : Elevators (H) - Machine Rooms (H)2 There are pipes that carry liquids, gases or vapors directly above the elevator controller. These pipes should be guttered to assure that no discharge from these pipes falls onto the elevator equipment.
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: The audible signal device did not sound when phase I was activated.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods On top of the elevator car, the cab steadier bushings shall be reinstalled to provide proper car clearance and more stable car.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x The rear car door restrictor device is located in the machine room and shall be installed so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. 4/3/2025