Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A MCP shall be provided for each unit and kept on site 3/26/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No After the third car modernization is finished, all covers on electrical boxes shall be installed. 5/27/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 Yes No All cross wiring connections shall be complete. 5/27/2025
MO Minimum : Elevators (I) - Pits (I)1 No No All pits shall be kept dry & clean and free of equipment or material not relating to the operation of the elevator 3/26/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Cab lighting needs to be guarded. 5/9/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) Yes No Car door restrictor does not work. 5/7/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Clean elevator pit. 7/21/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevator was not running at scheduled test date. Repair elevator and perform annual no load test of elevator. 1/5/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Emergency generator test needs to be witnessed when all Modernizations are completed. 5/27/2025
conversion conversion n/a No No Emergency phone not working 5/9/2019
conversion conversion n/a No No Pits shall be clean 5/9/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes No Suspension ropes are below minimum diamter. 5/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No Written maintenance control program shall be kept on site for each elevator. 6/15/2021