Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)12 (Door open zones) x Car door restrictor does not work. 5/7/2020
MO Minimum : Elevators (D) - Brakes (D)2 x x Replace contaminated machine brake shoes. 2/27/2019
MO Minimum : Elevators (E) - Machines (E)1 Repair or replace machine drive sheave. 5/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Rear car door restrictor does not work. Repair 1/5/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Alarm bell does not work on battery back-up. 5/25/2021
MO Minimum : Elevators (I) - Pits (I)1 Elevator pit has trash and debris in it. Clean elevator pit 3/27/2024
MO Minimum : Elevators (I) - Pits (I)1 Pits shall be kept dry, clean & free of equipment or material not relating to the operation of the elevator 3/26/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Provide additional relay to separate the shunt trip function between the 2 hoistways. Shunt to only activate when heat detector in the respective hoistway is triggered. 10/18/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked. 10/18/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability x Phone monitoring will be added to duplex lobby. When all three are completed, push button station must be checked.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Top of hoistway smoke needs to be programmed correctly to go to primary floor. 10/18/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x Only one smoke detector in the shared machine room for all three elevators. Provide additional smoke detectors to achieve proper coverage. 10/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program shall be kept on site for each elevator. 6/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program not on site 6/7/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A MCP shall be kept for each unit and kept on site 3/27/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x All three elevators will have emergency generator power. Emergency power shall be tested once modernizations are complete. 10/18/2024
conversion conversion conversion - reinspect x Emergency bell does not work 2/7/2019
conversion conversion n/a Pits shall be clean 5/9/2019