MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
In car emergency phone shall work on battery power.
|
3/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
A smoke detector, alarm horn, and strobe shall be permanently anchored in the pit. Currently hanging in the pit creating a head clearance issue.
|
3/18/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room is expired. A current tested, ABC type fire extinguisher shall be provided in the machine room.
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
11/17/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Recommendation: A pressure switch shall be provided in the line between the cylinder and the valve which shall be activated by the loss of positive pressure at the top of the cylinder. Note: This unit is governed by MO Minimums code, which does not specifically require a pressure switch.
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Machine room has excessive water in it. Water shall not be allowed to accumulate on the machine room floor. Correct source of leak.
|
8/20/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)7
|
|
|
All machine room wiring shall be enclosed. Note: Box covers are missing and wiring is exposed.
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Water shall not be allowed to accumulate on the machine room floor.
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lights shall be operational. Note: Both machine room lights must work.
|
11/17/2022
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be operational.
|
2/7/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
The machine room lighting shall be operational and shall provide a minimum of 10 foot candles at the floor level and in front of the controller.
|
11/17/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The trash can full of trash and the abandoned fire pull station located in the pit shall be removed.
|
11/17/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Phase 1 lobby key switch shall work.
|
3/18/2019
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
8/25/2022
|
conversion
|
conversion
|
n/a
|
|
|
Car emergency lighting shall work.
|
3/18/2019
|
conversion
|
conversion
|
n/a
|
|
|
Car emergency telephone needs to be re-programmed to the new elevator contractor.
|
3/18/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
11/17/2022
|