Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Car emergency lighting shall work. 3/18/2019
conversion conversion n/a Car emergency telephone needs to be re-programmed to the new elevator contractor. 3/18/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase 1 lobby key switch shall work. 3/18/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency phone shall work on battery power. 3/18/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements A smoke detector, alarm horn, and strobe shall be permanently anchored in the pit. Currently hanging in the pit creating a head clearance issue. 3/18/2019
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be operational. 2/7/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x The auxiliary power lowering operation shall be functional. 8/25/2022
MO Minimum : Elevators (H) - Machine Rooms (H)7 All machine room wiring shall be enclosed. Note: Box covers are missing and wiring is exposed. 11/17/2022
MO Minimum : Elevators (I) - Pits (I)1 The trash can full of trash and the abandoned fire pull station located in the pit shall be removed. 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Water shall not be allowed to accumulate on the machine room floor. 11/17/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Recommendation: A pressure switch shall be provided in the line between the cylinder and the valve which shall be activated by the loss of positive pressure at the top of the cylinder. Note: This unit is governed by MO Minimums code, which does not specifically require a pressure switch. 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lighting shall be operational and shall provide a minimum of 10 foot candles at the floor level and in front of the controller. 11/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room is expired. A current tested, ABC type fire extinguisher shall be provided in the machine room. 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) The machine room lights shall be operational. Note: Both machine room lights must work. 11/17/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room has excessive water in it. Water shall not be allowed to accumulate on the machine room floor. Correct source of leak. 8/20/2024