MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
A pit ladder is required in all pits that have a depth of 4' or more. The ladder shall extend not less than 30" above the sill of the access door, or hand grips shall be provided to the same height. The ladder shall be permanently attached and be made of noncombustible material.
|
6/17/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Correct leaks under the hydraulic tank.
|
6/17/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be posted in the elevator machine room.
|
6/17/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
10/27/2021
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The wire-way in the hoist-way shall be properly enclosed. (The Unistrut/wire-way running the entire length of the hoist-way shall have covers installed.)
|
10/27/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/27/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
MCP Fire service testing must be properly documented monthly on log sheet.
|
5/31/2024
|