Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators connected to an emergency or standby generator shall be tested for operation on emergency or standby power. Re-inspection required 11/7/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase I did not initiate when the firemen's emergency service key was turned to the "on" position. Only elevator that services the emergency room. Phase I works, 15 days to repair phase I or unit will be Red-tagged. Re-inspection required