Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational, needs repaired. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation Written maintenance control program shall be kept on site for each elevator. 2/10/2021
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake x x The rope gripping device that is installed on this unit to conform for unintentional movement of the elevator car is not activating. The device shall be repaired or replaced and a reinspection is required. If the device is replaced an alteration permit and inspection is required. 10/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. 10/9/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts A security key switch bezel is pushed in at the landings on G1 and lobby resulting in a possible electrical hazard and shall be repaired. 6/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means, broken-suspension-member detection means, residual-strength detection means, and related circuits. 6/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates A security key switch bezel is pushed in at the landings on G1 and lobby resulting in a possible electrical hazard and shall be repaired. 6/18/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) Unusual testing procedures not outlined in A17.2 shall be present and accessible according to this code section. These include, but not limited to procedures for tests, periodic inspections, maintenance, replacements, adjustments, and repairs for traction-loss detection means. broken-suspension-member detection means, residual strength detection means, and related circuits. 6/18/2024