Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on site written maintenance control program.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform test on or before next annual inspection.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x Unsealed. See 4/23/21 report. 2/6/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Expired
A17.1-1996 : Elevators 2.32 - Control Valve 303 Car failed 15 minute stand test. Tech determined leaking back through valve. Repair/replace as needed. Reinspect.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) Floor’LL’ (r) braille/tactile plate missing, replace.
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing x See ‘21 report for OSV. THIRD NOTICE 11/13/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate.
A17.1-1996 : Elevators 2.32 - Control Valve 303 Car failed 15 minute stand test, repair as needed. SECOND NOTICE.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) x OSV valve is not sealed and due for the full load test and tripping speed checked. Re-inspection required
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room