A17.1-1996 : Elevators
|
1.15 - sign and operating device symbols
|
1001.2(a)(15)
|
|
|
Floor’LL’ (r) braille/tactile plate missing, replace.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
Sump hole filled with oil, remove. Determine if sump pump works, if not replace.
|
|
A17.1-1996 : Elevators
|
2.32 - Control Valve
|
303
|
|
|
Car failed 15 minute stand test. Tech determined leaking back through valve. Repair/replace as needed. Reinspect.
|
|
A17.1-1996 : Elevators
|
2.32 - Control Valve
|
303
|
|
|
Car failed 15 minute stand test, repair as needed. SECOND NOTICE.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Expired
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide on site written maintenance control program.
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Perform test on or before next annual inspection.
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
x
|
|
See ‘21 report for OSV. THIRD NOTICE
|
11/13/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
OSV valve is not sealed and due for the full load test and tripping speed checked. Re-inspection required
|
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspection)
|
x
|
|
Unsealed. See 4/23/21 report.
|
2/6/2023
|