MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)4
|
|
|
Pit bucket for one of the jacks was overflowing, log says that it was last emptied in December, schedule packing replacement
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.11.3.1.5(c)
|
|
|
needs buckets to catch oil from pistons, needs drain lines for each piston
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
repair the emergency light system, emergency lights and bell did not work on battery power, replace battery. A17.1-2016 2.14.7.1.3
|
6/22/2023
|
conversion
|
conversion
|
n/a
|
|
|
Provide means to collect oil from holess jack heads, oil is running down side of cylinders onto the pit floor
|
8/20/2020
|