Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 110 disconnect in machine room is not lockable type. 4/25/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency bell does not work. 3/8/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light do not work. 11/18/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 12/6/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Machine room shall not be used for storage. 9/8/2020
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) Machine space shall not be used for storage of non-elevator equipment. 2/12/2021
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Need maintenance control program. 9/8/2020
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Pit shall be kept clean and dry. 9/8/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written maintenance control program shall be kept on site for each elevator. 2/12/2021