MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone shall work.
|
2/27/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
During the 15 minute standing test, the car dropped 12 inches. Need to determine where oil is leaking to. Red tagged and removed from service. Re-inspection required
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Hydraulic control valve in machine room is leaking hydraulic fluid. needs repair
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
During the 15 minute standing test, the car dropped 12 inches. Need to determine where oil is leaking to. Red tagged and removed from service. Re-inspection required
|
11/24/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Hydraulic control valve in machine room is leaking hydraulic fluid. needs repair
|
11/24/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
11/24/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water & debris from elevator pit
|
11/24/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water and debris from elevator pit.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
x
|
The testing could not be completed on the elevator at this time. This elevator was placed out of serviced and red tagged in 2022. In doing so, this elevator became “inactive”. An elevator can only remain in “inactive” status for 2 years. The elevator shall be returned to service or the elevator shall be decommissioned according to the State of Missouri requirements (per Missouri Division of Fire Safety MEMORANDUM 003-3) Currently the power is disconnected and only a machine room inspection could be performed.
|
|