| MO Minimum : Elevators | (I) - Pits | (I)1 |  |  | Remove water & debris from elevator pit |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance |  |  | During the 15 minute standing test, the car dropped 12 inches. Need to determine where oil is leaking to. Red tagged and removed from service. Re-inspection required |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance |  |  | Hydraulic control valve in machine room is leaking hydraulic fluid. needs repair |  | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) |  |  | A copy of the MCP shall be kept in the machine room for each elevator |  | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x |  | Emergency phone shall work. | 2/27/2019 |