Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) x The controller shall be properly grounded per NEC. 9/3/2019
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 1001.2(b)(8) x Disconnects shall be properly grounded per NEC. 9/3/2019
A17.1-1996 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 1001.2(b)(10) x Properly label feeder locations, panel name, and breaker numbers. 9/3/2019
A17.1-2016 : Elevators 7.19 - Maintenance records 8.6.1.2.1(a) Need maintenance control program on site posted on controller 5/11/2021