Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection The use of oil recovery systems back to the tank prevents proper monitoring of oil loss from packing gland. 8/15/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed.
MO Minimum : Elevators (H) - Machine Rooms (H)8 The lockable disconnect for the elevator cab lights does not disconnect the power as noted. Repair the disconnect to operate as designed.