Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of current state operating certificate needs to be properly displayed in machine room
MO Minimum : Elevators (A) - Hoistways (A)3 Basement and main floor doors are missing pick up rollers. 12/3/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Clean excessive oil from pump unit drip pan
conversion conversion conversion - reinspect x Emergency alarm bell shall work. 5/2/2019
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required 4/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Overspeed valve is not sealed and needs full load test and tripping speed checked. Second notice