Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No The muffler on the pumping unit is leaking and shall be replaced or repaired 1/5/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Remove water from pit and check sump pump operation. 6/11/2026
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 No No Power Unit catch can is full. Remove oil and repair leak(s) from the muffler. 6/11/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Overspeed valve is not sealed and needs full load test and tripping speed checked. Second notice 4/16/2025
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV is not sealed and needs full load test and tripping speed checked. Re-inspection required 4/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No OSV is not sealed and needs a full load test and tripping speed checked. Re-inspection required 2/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Need to clean excessive oil from pump unit drip pan 1/5/2026
conversion conversion conversion - reinspect Yes No Emergency alarm bell shall work. 5/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Clean excessive oil from pump unit drip pan 1/5/2026
MO Minimum : Elevators (A) - Hoistways (A)3 No No Basement and main floor doors are missing pick up rollers. 12/3/2020
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Any pipes conveying liquids, gas, or vapors cross the overhead of the elevator equipment shall be guarded or guttered. 6/11/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 1/5/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of current state operating certificate needs to be properly displayed in machine room 1/5/2026