Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide a code compliant MCP including onsite documents. 4/28/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room. 4/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) MCP evacuation procedures are required on-site. 5/5/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 5/5/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display the current state operating certificate in the elevator machine room. 4/28/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces There are signs of black mold in the machine room on sheet rock wall at bottom. Take corrective action as needed. 7/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces There are signs of black mold in the machine room on sheet rock wall at bottom. Take corrective action as needed. Violation still remains after 5/17/24 re-inspection. 7/29/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The personnel answering the emergency phone shall be able to provide the location of the elevator. 10/18/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone shall work. 5/17/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Battery lowering shall work. 5/17/2024