Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 1/23/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need a maintenance control program on site 1/23/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 11/29/2023
conversion conversion conversion - reinspect x Test emergency power when all elevator modernizations are complete. 1/24/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements x Counterweight runby(13.5") exceeds OEM maximum of 12" , as displayed on Pit Signage.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) PM/Repair/callback logs not being consistently documented. (2024/2025 blank except Annual Test dates)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly.