Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post the current state operating certificate in the elevator machine room. 4/27/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 12/6/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works, but video/text "yes/no" buttons are not working properly. 5/28/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) Yes No Make car door restrictor operational. 3/29/2019
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) Yes No Provide code compliant minimum counterweight runby. 5/4/2020
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current operating certificate shall be displayed in the equipment room in a non0-combustible frame.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation No No Fire service testing must be properly documented monthly on log sheet located in the MCP.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. The voice works, but video/text not working properly, answering person cannot activate camera or text/screen.
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 Yes No Rope gripper wear swtich indicates gripper needs to be replaced. Will not reset without assistance.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Yes No The barrier in the overhead shall be restored so that no opening exists. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.20.2 Yes No A suspension rope tag shall be installed. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.27 - Crosshead data plate 2.20.2 Yes No A governor rope tag shall be installed. 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices Yes Yes 2.27.3.2.1(c) - The smoke detector in the top of the hoistway shall only be used where sprinklers are installed. The smoke detector in the top of the hoistway shall be removed. 4/9/2021
conversion conversion n/a No No Replace broken roller guide assembly. 2/13/2019