A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Make car door restrictor operational.
|
3/29/2019
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
Provide code compliant minimum counterweight runby.
|
5/4/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
The barrier in the overhead shall be restored so that no opening exists.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.27 - Crosshead data plate
|
2.20.2
|
x
|
|
A suspension rope tag shall be installed.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.27 - Crosshead data plate
|
2.20.2
|
x
|
|
A governor rope tag shall be installed.
|
4/9/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
2.27.3.2.1(c) - The smoke detector in the top of the hoistway shall only be used where sprinklers are installed. The smoke detector in the top of the hoistway shall be removed.
|
4/9/2021
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work. The voice works, but video/text "yes/no" buttons are not working properly.
|
5/28/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
6/3/2024
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post the current state operating certificate in the elevator machine room.
|
4/27/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
12/6/2021
|
conversion
|
conversion
|
n/a
|
|
|
Replace broken roller guide assembly.
|
2/13/2019
|