Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - A monthly fire service testing log shall be kept on-site. 10/2/2019
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 4x4 electrical box in machine room needs to have wiring inside box and cover installed. There are multiple boxes in this condition on the wall and ceiling. 11/15/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of main 120v power. 11/15/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall call support line that is available 24/7, answered by authorized and trained individuals, and shall provide proper location message. 11/15/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 11/15/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 An elevator maintenance log shall be kept in the elevator machine room. 10/2/2019
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 11/15/2023