Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys Need to test stop switch on fire service. No key on site. 12/30/2020
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x Ropes are undersized. Repair within 15 days. 9/3/2020
A17.1-1996 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10.1.2 - Protection not functioning x Controller has seismic feature, but is not wired. 7/7/2021