Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) The controller air conditioning shall be operational.
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) The elevator machine room shall be protected from the weather. (Note: Windows are being left open, and the equipment and machine room floor are showing signs that they have been wet, possibly from a leaky roof).
A17.1-1996 : Elevators 1.15 - sign and operating device symbols 1001.2(a)(15) The car identification number shall be painted on, engraved, or securely attached to the car operating panel and shall be a minimum of 1/2" in height. (Note: The COP currently doesn't have an identification number and is required since this car shares a machine room with cars 1 & 2).
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Suspension rope tail ends shall be properly seized/banded and retaining clips shall be set at proper distance.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Replace missing hoistway door guides.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Reinstall controller AC Cover
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current state operating permit shall be obtained and displayed in the equipment room.
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 MCP fire service testing must be properly documented monthly on log sheet.
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 Pit 4x4 electrical box is missing cover. Exposed wiring.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Repair loose pickup assembly on 1st floor door.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x x 2-way communication device still not working. The building is vacant, therefore the elevator is red tagged.
conversion conversion n/a Machine room roof leaks and drips on elevator equipment. The roof leak shall be repaired. 4/22/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code All lighting in the machine room shall be operational. 5/21/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) A current tested ABC type fire extinguisher shall be provided in the elevator machine room. Current extinguisher is expired. 5/21/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 5/13/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work, with and without main power, and give proper location. 10/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete due to unit shutting down during inspection. Weight portions of test at 125%, 100% safeties, slide, and 100% car buffer remaining. 10/26/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete. Elevator shutdown during testing. Need to test: Emergency light, alarm, and phone. 12/5/2024