MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Remove oil from pit channel
|
8/13/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
No
|
No
|
Clean oil in pit
|
1/13/2025
|
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
Emergency communication inoperable. Re-inspection required
|
5/23/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
No
|
No
|
Test overspeed valve (unsealed) due before next inspection
|
8/13/2024
|
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
No
|
No
|
Provide current year tested fire extinguisher in the elevator machine room.
|
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
211.7 Firefighter' Service Operating Procedures
|
No
|
No
|
Post Phase I instructions near the f/f switch in the lobby.
|
|