conversion
|
conversion
|
n/a
|
|
|
Install permanent light fixture and switch in pit.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Pipes conveying liquids, vapors,gases not allowed in hoistway.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Install pit ladder with handrails extending 30 inches above landing
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Cover exposed motor leads in machine room.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Post current operating certificate.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Machine room door shall be self closing and self locking.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
No annual testing or inspection 2009 to 2001 and 2014 to 2017 per state website. No test tags on site for those years either.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Machine room fire extinguisher not certified.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Emergency light and bell do not operate.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Guard hoistway windows and mark HOISTWAY viewable from outside.
|
7/15/2020
|
conversion
|
conversion
|
n/a
|
|
|
Provide maintenance control plan
|
|