Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Install permanent light fixture and switch in pit. 7/15/2020
conversion conversion n/a Pipes conveying liquids, vapors,gases not allowed in hoistway. 7/15/2020
conversion conversion n/a Install pit ladder with handrails extending 30 inches above landing 7/15/2020
conversion conversion n/a Cover exposed motor leads in machine room. 7/15/2020
conversion conversion n/a Post current operating certificate. 7/15/2020
conversion conversion n/a Machine room door shall be self closing and self locking. 7/15/2020
conversion conversion n/a No annual testing or inspection 2009 to 2001 and 2014 to 2017 per state website. No test tags on site for those years either. 7/15/2020
conversion conversion n/a Machine room fire extinguisher not certified. 7/15/2020
conversion conversion n/a Emergency light and bell do not operate. 7/15/2020
conversion conversion n/a Guard hoistway windows and mark HOISTWAY viewable from outside. 7/15/2020
conversion conversion n/a Provide maintenance control plan
MO Minimum : Elevators (H) - Machine Rooms (H)2 PROVIDE A SELF CLOSING / SELF LOCKING MACHINE ROOM DOOR
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) INSTALL A PIT LIGHT AND A GFCI OUTLET
MO Minimum : Elevators (I) - Pits (I)5 INSTALL A PIT LADDER
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate DISPLAY STATE OPERATING CERTIFICATE IN MACHINE ROOM
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x PROVIDE A WORKING IN CAR EMERGENCY PHONE
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x THE INSTALLED PHONE IS NOT WORKING 3/20/2025