A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Door restrictor not working.
|
12/31/2025
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
112.3d
|
x
|
x
|
Test of fire service needs to be conducted upon reinspection.
|
12/31/2025
|
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
206
|
x
|
x
|
Governor will not set safeties. Cable slips through the jaws.
|
12/31/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
Car has not been inspected since 12/27/2018 and the last 5 year was performed 11/1/2016. Unit needs to be inactive on state data base and decommissioned or repaired and inspected.
|
3/18/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
Performed inspection to place unit into INACTIVE STATUS. Unit must have all violations corrected after two years or to be placed into OUT OF SERVICE status after meeting all the requirements to do so.
|
|