A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Door restrictor not working.
|
12/31/2025
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
112.3d
|
x
|
x
|
Test of fire service needs to be conducted upon reinspection.
|
12/31/2025
|
|
A17.1-1996 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
206
|
x
|
x
|
Governor will not set safeties. Cable slips through the jaws.
|
12/31/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
Car has not been inspected since 12/27/2018 and the last 5 year was performed 11/1/2016. Unit needs to be inactive on state data base and decommissioned or repaired and inspected.
|
3/18/2026
|