Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x alarm bell not working, 6/20/2019
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Back wall of car broken loose in places 4/9/2019
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 keep ceiling exit shut--safety hazard 4/9/2019
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 No emergency exit locking hatch due to a solid fixed ladder mounted to the rear wall that provides full time access to the rusted,flimsy car top covered with open wiring not in conduits,no covers on boxes or troughs.
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)4 Car top is covered in rust and is extremely flimsy and is highly recommended to be replaced entirely.
MO Minimum : Elevators (H) - Machine Rooms (H)4 Could not perform stop ring test due to excessive water on machine room floor.
MO Minimum : Elevators (I) - Pits (I)1 x this pit is full of oil and bio-hazardous chicken processing fluids. there is no means of oil collection per A17.1 1996 302.g. recent addition of 5 gallons of hydraulic fluid to the system on 3/3 2021 in order to reach top floor, became evident that at least that much oil leaked overnight. Undetermined cause of oil loss caused me to take this unit out of service until such time as to the cause of fluid leak can be further explored. left unit on the buffers with main line valve closed and Red Tag applied to disconnect 3/29/2021
conversion conversion n/a Keep ceiling exit closed--safety issue 7/20/2018