All phase 1 and phase 2 fire service key switches must e keyed alike in the same building. Reinspetion required. Key is FEOK1
|
11/16/2018
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a
|
x
|
|
Clean out all non-elevator parts from pit.
|
2/19/2020
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1001.2(b)(7)
|
|
|
Fire extinguisher needs to be serviced.
|
12/13/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Insulation jacket on traveling cable is damaged with exposed wiring in multiple places, need to replace traveling cable
|
|
conversion
|
conversion
|
n/a
|
|
|
Oil return line missing inside of hydraulic pump unit. Repair. Note: oil is running down side of tank
|
12/13/2019
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit has 6 inches of oil and water in it, need to clean pit
|
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
1001.2(a)(18)
|
x
|
|
Repair car door restrictor.
|
2/19/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair inoperative emergency phone. Phone line has busy signal when activated.
|
9/24/2019
|
A17.1-1996 : Elevators
|
3.8 - Top emergency exit
|
1001.2(c)(12)
|
|
|
Repair latch on escape hatch.
|
12/13/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
x
|
x
|
Right cylinder O-ring around head failed during pressure testing. Red-tagged and removed from service. Re-inspection required
|
11/4/2024
|