Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion conversion - reinspect x All phase 1 and phase 2 fire service key switches must e keyed alike in the same building. Reinspetion required. Key is FEOK1 11/16/2018
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a x Clean out all non-elevator parts from pit. 2/19/2020
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Fire extinguisher needs to be serviced. 12/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Insulation jacket on traveling cable is damaged with exposed wiring in multiple places, need to replace traveling cable
conversion conversion n/a Oil return line missing inside of hydraulic pump unit. Repair. Note: oil is running down side of tank 12/13/2019
MO Minimum : Elevators (I) - Pits (I)1 Pit has 6 inches of oil and water in it, need to clean pit
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 1001.2(a)(18) x Repair car door restrictor. 2/19/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair inoperative emergency phone. Phone line has busy signal when activated. 9/24/2019
A17.1-1996 : Elevators 3.8 - Top emergency exit 1001.2(c)(12) Repair latch on escape hatch. 12/13/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance x x Right cylinder O-ring around head failed during pressure testing. Red-tagged and removed from service. Re-inspection required 11/4/2024