Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No The emergency power shall be tested with 125% of capacity. 7/28/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency/standby power operation of the elevators shall be operational. 11/9/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/26/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. 4/26/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor shall work. Bracket is missing. 6/26/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 6/26/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/18/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No MCP Fire Service testing must be properly documented monthly on log sheet. 6/30/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Expired State operating certificate in the machine room. 3/25/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing incomplete. Need to test: FS, EP, EQ, SOS, Buffers (car/CW), 100% safeties, 125% (hold & 1 floor run), slide. 3/25/2024