MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.9 Cleaning of Top of Cars
|
|
|
The top of car shall be kept clean.
|
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1
|
|
|
The pit shall be kept clean. Remove excess debris & oil.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Replace missing hall fire signage, "in case of fire" (C Level).
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
The emergency power shall be tested with 125% of capacity.
|
7/28/2019
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
Suspension ropes have stretched to a point where the elevator will not hit the top final limit switch. The suspension ropes shall be shortened.
|
7/28/2019
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Emergency/standby power operation of the elevators shall be operational.
|
11/9/2021
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing.
|
4/26/2022
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
4/26/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Car door restrictor shall work at all floors.
|
6/26/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
6/26/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
|
7/18/2023
|