Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit shall be kept clean and dry. 5/6/2020
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The emergency light shall work. 5/6/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be displayed in the elevator machine room. 12/9/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide a code compliant MCP including onsite documents. 12/9/2025
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that is not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. 12/9/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO state operating certificate shall be displayed in the elevator machine room. 12/9/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No The pit shall be kept clean and dry. Remove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. 12/9/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/9/2025
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/9/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit has no lighting. Fixture should provide an illumination of at least 5fc at the pit floor. 12/9/2025