Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational with 24/7 support. 11/4/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 7/26/2021
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No The machine room lighting shall be operational. 7/26/2021
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) No No Fire extinguisher is out dated.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No The machine room lights shall be guarded. 3/15/2024
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No The machine room lights shall be operational. 3/15/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit shall be kept clean and dry. Remove water and clean the pit. 7/26/2021
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept on site. 3/15/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No The cab lighting guards are missing and shall be replaced. Lighting shall be guarded or covered. 7/26/2021
A17.1-1996 : Elevators 1.17 - Standby power operation 207.8 Yes No Emergency power must be tested annually.
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/27/2024
A17.1-1996 : Elevators 2.14 - Code data plate 215 No No The code data plate required by A17.1 2016, 2016 8.9 shall be provided in plain view, securely attached to each main line disconnect or controller. 3/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 2/27/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/10/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display a copy of the current state operating certificate. 3/15/2024
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate. 11/21/2018
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No The in-car stop switch shall not be rendered inoperative on phase one fire service until the car is in motion. 2/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) No No Evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 3/15/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/13/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No The data on the MCP shall be filled out as required by A17.1 2016 8.6.1.4.1(a)(3). 3/15/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 3/13/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) Yes No A category 5 test of the overspeed valve shall be performed within 90 days. 3/15/2024
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) Yes No The overspeed valve is not sealed and has been previously cited that a category 5 test is needed. A category 5 test shall be performed within 90 days. 2/27/2024