Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency lights and alarm not working, phone ok. 5/29/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working, alarm bell ok. 5/28/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current operating cirt. displayed 9/16/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.2-211.8 Yes Yes no smoke detectors in mach room or in the hallway. 5/11/2021
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 No No no sump pump cover 1061b(4) 9/16/2022
MO Minimum : Elevators (I) - Pits (I)8 No No Provide a non combustable cover for sump pump in pit. 5/27/2026
MO Minimum : Elevators (I) - Pits (I)8 No No Provide non combustable cover for sump pump in pit. 9/16/2022
MO Minimum : Elevators (I) - Pits (I)8 No No Provide non combustable cover for sump pump in pit. 9/16/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Provide smoke detectors in each elevator lobby, and machine room. 10/5/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Smoke detectors present, but not connected to the controller. Complete installation, and re-inspect. 5/9/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 102 Yes No sump pump pluged into GFI outlet in pit no non gfi out let for sump pump 5/11/2021