Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Existing battery lowering unit does not work. 3/2/2022
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Perform test on or before next annual inspection. 3/10/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide on-site maintenance control program. 3/10/2025
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 1206.2a (Pits and Hoistways) Clean pit (oil). 3/10/2025
A17.1-1996 : Elevators 5.11 Plunger and Cylinder 1206.5b(4) Packing is worn and leaking, repair as needed. 4/7/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1002.2g (Standby Power Operation) x Failed Cat 1 Standby power test. Re-inspection required 9/26/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Unsealed. 4/7/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Battery backup lowering unit not working, repair as needed. 4/7/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display update Missouri Operating Certificate in machine room 3/10/2025
MO Minimum : Elevators (I) - Pits (I)1 clean pit (oil) 3/10/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 3/10/2025