| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) |  |  | A written copy of the MCP shall be kept in the machine room for each elevator |  | 
                
                    | MO Minimum : Elevators | (O) - Existing Hydraulic Elevators | (O)4 (Re-Inspection) | x |  | Car failed 15 minute stand test. Tech determined to be leaking back through the valve. Repair/replace as needed. | 2/3/2023 | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | x | Elevator will not recall to designated landing when removed from Phase II and cannot reset. Red-tagged, removed from service. Re-inspection required | 3/19/2024 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x |  | Emergency phone does not work. | 3/22/2022 | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x |  | Not working correctly. | 2/3/2023 | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x |  | Phase II operation not correct, repair as needed. | 2/3/2023 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation |  |  | Provide MCP. |  |