ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
Provide feeder locations on main line connects.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
8.11.2.1.2(o)
|
x
|
|
Provide testing of machine brake with 125% capacity.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
Provide code compliant machine room lighting. Currently measured at 14.5fc.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
Provide GFCI type receptacle on lower part of machine room.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
x
|
|
Provide complete MCP.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
x
|
|
Remove all non-elevator related materials from the machine room.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
8.11.2.1.2(h)
|
x
|
|
Secure wires hanging down from over the machine room door.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
8.11.2.1.3(z)
|
x
|
|
Provide governor rope data tag.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
x
|
|
Provide hoist rope data tag.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
8.6.4.11
|
x
|
|
2.10.2 - Provide car top railing system, as needed.
|
1/31/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
8.11.2.1.3(o)
|
x
|
|
Provide numbering on the car top.
|
1/31/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Must have current certificate in machine room.
|
|