Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Cwt. run-by is 14.00". Maximum allowed by manufacture is 12.00". 7/17/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Temp wiring shall be removed for the push buttons. 2/6/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 2.1.1 x Seal all hoistway penetrations. 2/6/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 8.11.3.1.5 (j) Car Safety x Safety slide too long. 2/6/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Must have current certificate in machine room.