Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability No No Phone Failed 6/7/2024
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No Missing Phase i Instruction 6/7/2024
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post updated certificate 6/7/2024
A17.1-2016 : Elevators 2.1 - Access to machine space 8.11.3.1.2(b) No No Door to be self closing & self locking 2.7.3.4.1 (a) 6/7/2024
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.2.1.1(e) No No Must make Emergency light operable. 1.5 6/7/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make Emergency Alarm operable. 1.6 3/24/2022
A17.1-2016 : Elevators 1.15 - sign and operating device symbols 8.6.1.6.7 No No Must provide missing phase I fire service instructional signage. 8.6.1.6.7 6/7/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Must make emergency phone operable. 8.6.4.15 7/10/2023
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No Must Make Emergency phone operable. 8.6.4.15 5/10/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Must post current State operating Cert. 5-100(2) 6/7/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Must post Current state operating Cert. 6/7/2024