Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x The counterweight is within 1 inch of touching the oil buffer when the elevator travels to the top floor. The counterweight buffer has a buffer switch that will activate when the oil buffer is compressed thereby resulting in a elevator shut down. The hoist ropes shall be shortened to provide a minimum runby of 6 inches. 5/14/2020
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Provide annual testing of elevator recall and power selector switch on standby power operation. 2/17/2021
A17.1-1996 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 1001.2(e)(2) x Provide current code compliant runby 9/14/2022
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean pit
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Provide cat 5 generator test 9/14/2022
A17.1-1996 : Elevators 4.12 - Standby power selection switch 1001.2(d)(12) Provide testing of generator selector switch
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Hoistway door missing bottom door guide, 10th floor left door
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) Clean car top
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1002.2f x Provide phase 1 and 2 testing 9/14/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Door restrictor inoperable. Re-inspection required 3/8/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the machine room
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule for emergency power test. Re-inspection required
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.6.4.11 Runby (Re-Inspect) x Runby shall be adjusted to maintain at least 6" of runby. Re-inspection required 3/8/2023
MO Minimum : Elevators (A) - Hoistways (A)3 Fire tabs shall be installed on 1st floor doors
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be cleaned, including hoistway & cartop
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated Missouri Operating Certificate in machine room