A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
106.1e Illumination of Pits
|
|
|
Clean pit
|
|
A17.1-1996 : Elevators
|
4.12 - Standby power selection switch
|
1001.2(d)(12)
|
|
|
Provide testing of generator selector switch
|
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Hoistway door missing bottom door guide, 10th floor left door
|
|
A17.1-1996 : Elevators
|
2.5 - Housekeeping
|
1001.2(b)(5)
|
|
|
Clean car top
|
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Fire tabs shall be installed on 1st floor doors
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be cleaned, including hoistway & cartop
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be on display in the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display updated Missouri Operating Certificate in machine room
|
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Provide annual testing of elevator recall & power selector switch on standby power operation. Reschedule for emergency power test. Re-inspection required
|
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1002.2f
|
x
|
|
Provide phase 1 and 2 testing
|
9/14/2022
|
A17.1-1996 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
111.5 Restricted Opening of Hall/Car Doors
|
x
|
|
Door restrictor inoperable. Re-inspection required
|
3/8/2023
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11 Runby (Re-Inspect)
|
x
|
|
Runby shall be adjusted to maintain at least 6" of runby. Re-inspection required
|
3/8/2023
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
1001.2(a)(17)
|
x
|
|
Provide cat 5 generator test
|
9/14/2022
|
A17.1-1996 : Elevators
|
3.23 - Suspension rope
|
1001.2(c)(29)
|
x
|
|
The counterweight is within 1 inch of touching the oil buffer when the elevator travels to the top floor. The counterweight buffer has a buffer switch that will activate when the oil buffer is compressed thereby resulting in a elevator shut down. The hoist ropes shall be shortened to provide a minimum runby of 6 inches.
|
5/14/2020
|
A17.1-1996 : Elevators
|
1.17 - Standby power operation
|
211.2
|
x
|
|
Provide annual testing of elevator recall and power selector switch on standby power operation.
|
2/17/2021
|
A17.1-1996 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
1001.2(e)(2)
|
x
|
|
Provide current code compliant runby
|
9/14/2022
|