Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 5/12/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 5/12/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room shall be self-closing and self-locking and operable from the interior space without the use of a key. 3/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The code data plate required by A17.1 2016, Section 8.9, shall be provided in plain view, securely attached to each main line disconnect or controller. 5/12/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 The network cables passing through the machine room shall be enclosed and separated from the machine room or the network cables shall be removed. 3/27/2024