ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.11.3.1.5 (j) Car Safety
|
x
|
|
A category 5 safety test shall be performed.
|
12/9/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
A code compliant ladder shall be installed in the elevator pit.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
1/26/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
A current tested fire extinguisher is required in the elevator machine room.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
x
|
|
An MCP shall be kept on-site.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display a current state operating certificate.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
Phase 2 fire service shall be operational. (Maintenance company attempted to fix, but unable to. Unit due for MOD in May 2020).
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
x
|
|
Properly fix the hole in the pit wall near piping.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Provide a written MCP.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5 Illumination of Pits
|
x
|
|
Provide code compliant pit lighting at all areas of the pit. The pit lighting shall be a minimum of 10 ftc.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
|
|
The car top light shall be operational.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
The door closing force shall be under 30 lbs.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency alarm bell shall be operational.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection)
|
x
|
|
The flashing hat feature on fire service shall be operational when the smoke detectors in the hoistway and machine room are activated.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.2 - Hoistway doors
|
8.11.2.1.4(b)
|
x
|
|
The gaps between the hoistway door panels and frames shall not exceed 3/8". If code compliant gaps cannot be achieved, a variance shall be applied for.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.22 - Wire rope fastening and hitch plate
|
8.11.2.1.3(bb)
|
x
|
|
The hoist ropes shall be properly secured in the shackles.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.11.2.1.2(e) (Re-Inspection)
|
|
|
The machine room shall not be used for the storage of non-elevator related material.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4 Access to Pit
|
x
|
|
The pit ladder shall be code compliant. If a code compliant pit ladder will not fit in the pit a variance shall be applied for.
|
12/16/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The pit shall be kept clean.
|
12/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.1 - Car platform guard
|
2.15.9
|
x
|
|
The toe guard shall be 48" long. If pit depth in inadequate to support a 48" toe guard a variance shall be applied for.
|
12/16/2020
|