Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Need a maintenance control program on site asap 8/9/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Incomplete test. Standby emergency power shall be tested, hoistway shall be ran, pit door and stop switch shall be tested, and fire service shall be tested. 2/17/2025
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Failed stand test, tank losing oil blown jack 1/6/2020
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)1 x x Door Pressure exceeds 30 lbs 1/6/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car door restrictor does not work, needs to be repaired. Re-inspection required 1/17/2025