Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/26/2022
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 No No A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. 4/26/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor shall work at all floors. 6/26/2023
A17.1-1996 : Elevators 3.2 - Car top light and outlet 204.7 No No Car top shall have lamp and guard. 3/21/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 6/26/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 Yes No Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/18/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No Emergency/standby power operation of the elevators shall be operational. 10/5/2021
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Expired State operating certificate in the machine room.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting No No Machine room lighting needs to be repaired. One or more bulbs is not working. 3/21/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Testing is incomplete. Began annual and Cat 5 testing, to be finished by another inspector. Items tested - Hoistway, door, gate, restrictor, cartop, pits, light, bell, phone, comp-sheave, ring & string, terminal limits. 3/12/2025
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) Yes No The emergency power shall be tested with 125% capacity. 7/28/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Two-way communication device shall work. Phone dials, no answer. 3/12/2025
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 4/26/2022