Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a All machine room lighting shall be operational. 10/1/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/21/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. The monthly fire service checklist is missing. 3/21/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Phase 2 switch Halo to be replaced. It is currently unreadable. 3/21/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit shall be kept clean. Remove excess debris. 3/21/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/18/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete: Began annual & Cat 5 testing, remaining testing to be finished by another inspector. Items tested - Hoistway, door, gate, restrictor, cartop, pits, light, bell, phone, comp-sheave, ring & string, terminal limits. 3/13/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. It dials out, but no answer. 3/13/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell shall work with loss of main 120v power. Bell is very weak. 3/13/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When testing fire service, the fire service key switch would not go onto "hold". Repair or replace the switch as needed. 5/12/2022
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor shall work at all floors. 6/26/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 6/26/2023
conversion conversion conversion - reinspect x Replace the hoist ropes. 4/23/2019
conversion conversion conversion - reinspect x Schedule a full lad test of the emergency power system on elevators 1-8. 4/23/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The emergency power shall be tested with 125% of capacity. 7/28/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency/standby power operation of the elevators shall be operational. 10/5/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When testing fire service, the fire service key switch would not go onto "hold". Repair or replace the switch as needed. 4/7/2022