Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures and monthly fire service checklist are missing. 4/26/2022
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 4/26/2022
A17.1-1996 : Elevators 3.9 - Floor and emergency identification numbering 211.9 COP shall display unit identifier (Elevator #7). 3/26/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit shall be kept clean. Remove excess debris. 3/26/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 7/18/2023
conversion conversion conversion - reinspect x Schedule a full lad test of the emergency power system on elevators 1-8. 4/23/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x The emergency power shall be tested with 125% of capacity. 7/28/2019
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Emergency/standby power operation of the elevators shall be operational. 10/5/2021
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car front door restrictor shall work at all floors. 6/26/2023
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 6/26/2023